GAS & FLAME products
Teledyne Detcon Inc.
Detecting the Difference
다양한 산업분야에 적용 가능 하도록 디자인된 가스 검출기 , 제어시스템 ,무선기술을 바탕으로 한 가스 검출기 등의 제품들을오래도록 축적된 경험을 바탕으로 제공해드리고 있습니다.
FP-700
Introduction
Model FP-700 is a non-intrusive “Smart” sensor designed to detect and monitor combustible gases in air over the range of 0-100% LEL using catalytic bead sensor technology. The plug-in, field replaceable detector is poison-resistant and features over-sized gold-plated connections that help prevent corrosion. The FP-700’s rugged framework includes an electro-polished 316 stainless steel housing with fully encapsulated electronics and dual layer surge protection. This innovative design virtually eliminates sensor failure due to water ingress, corrosion, vibration, and transient spikes. A primary feature of the Model FP-700 is embedded intuitive software that simplifies operator interface by guiding the user through routine calibration, configuration, and fault diagnostic functions using a built-in alpha/numeric display. The Model FP-700 is equipped with standard analog 4-20mA, and Modbus™ RS-485 outputs. Among its unique features is a wireless option that can be used with Detcon’s SmartWireless® product line. Additional integration options include a Remote Alarm Module (RAM), and HART. Detcon’s combustible gas sensor has an infinite shelf life and is supported by a 2-year warranty.
Specifications
Sensor Type : Continuous diffusion/adsorption , Matched-pair catalytic bead detector , Plug-in field replaceable
Sensor Life : 3 to 5 years typical
Measurement Range : 0-100% LEL (lower explosive limit)
Accuracy/Repeatability : ±3% 0-50% LEL; ±5% 50-100% LEL
Response/Clearing Time : T50 <10 seconds; T90 <30 seconds
Zero Drift : <5% per year
Outputs : Linear 4-20 mA DC , RS-485 MODBUS-RTU
Electrical Classification
Explosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°C to +75°C)
Class I, Zone 1, Group IIB+H2
ATEX
II 2 G Ex d IIB + H2 T4 Gb (Tamb = -40°C to +75°C)
Ingress Protection : NEMA 4X, IP66
Safety Approvals
CCSAUS Performance to ISA 12.13.01-2000 and CSA 22.2 #152
ATEX
CE Marking
SIL2 Certified to IEC 61508
Warranty
Plug-in detector - 2 years
Transmitter - 2 Years
Operating Temperature Range : -40°F to +167°F; -40°C to +75°C
Storage Temperature Range : -40°F to +167°F; -40°C to +75°C
Operating Humidity Range : 0-99% RH non-condensing
TP-700
Introduction
Specifications
Sensor Type : Continuous diffusion/adsorption , CHEMFET Solid State Metal Oxide Semiconductor , Plug-in field replaceable
Sensor Life : 5 to 10 years typical
Measurement Range : 0-20 ppm, 0-50 ppm, 0-100 ppm
Accuracy/Repeatability : ±10% of reading or ±2 ppm (greater of )
Response/Clearing Time : T50 <30 seconds; T80 <60 seconds
Outputs : Linear 4-20 mA DC , RS-485 MODBUS-RTU
Electrical Classification
Explosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°C to +75°C)
Class I, Zone 1, Group IIB+H2
ATEX
II 2 G Ex d IIB + H2 T4 Gb (Tamb = -40°C to +75°C)
Ingress Protection : NEMA 4X, IP66
Safety Approvals
CCSAUS Complies with ISA 92.0.01 Part 1-1998; Performance Requirements for H2S
ATEX
CE Marking
SIL2 Certified to IEC 61508
Warranty
Plug-in detector - 10 year conditional
Transmitter - 2 Years
Operating Temperature Range : -40°F to +167°F; -40°C to +75°C
FM ISA 92.0.01 Certified from : -40°C to +65°C for H2S
Storage Temperature Range : -31°F to +131°F; -35°C to +55°C
Operating Humidity Range : 5-100% RH non-condensing
Operating Pressure Range : Atmospheric ±10%
IR-700-CH
Introduction
Specifications
Sensor Type : Continuous diffusion/adsorption , Non-dispersive Infrared Optical (NDIR) - Combustible Gas , Sub-miniature plug-in field replaceable
Sensor Life : 5 years typical
Measurement Range : 0-100% LEL (lower explosive limit) , 0-100% by volume
Accuracy : ±2% F.S. (0-50% LEL)
Repeatability : ±2% F.S.
Response Time* : T50 < 6 seconds, T90 < 10 seconds
Zero Drift (typical) : ≤2% per 2 years
Outputs : Linear 4-20 mA DC , RS-485 MODBUS-RTU
Electrical Classification
Explosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°C to +75°C)
Class I, Zone 1, Group IIB+H2
ATEX
II 2 G Ex d IIB + H2 T4 Gb (Tamb = -40°C to +75°C)
Ingress Protection : NEMA 4X, IP66
Safety Approvals
CCSAUS Performance to ISA 12.13.01-2000 and CSA 22.2 #152
ATEX
CE Marking
SIL2 Certified to IEC 61508
Warranty
Plug-in detector - 5 year pro-rated
Transmitter - 2 Years
Operating Temperature Range : -40°F to +167°F; -40°C to +75°C
Storage Temperature Range : -40°F to +167°F; -40°C to +75°C
Operating Humidity Range : 0-100% RH non-condensing
DM-700 Series
Introduction
Product Available
DM-700-C2H2 Acetylene Sensor Assembly
DM-702-NH3 Ammonia Sensor Assembly
DM-700-AsH3 Arsine Sensor Assembly
DM-700-Br2 Bromine Sensor Assembly
DM-700-C4H6 Butadiene Sensor Assembly
DM-700-CO Carbon Monoxide Sensor Assembly
DM-700-CL2 Chlorine Sensor Assembly
DM-701-CLO2 Chlorine Dioxide Sensor Assembly (0-1ppm)
DM-700-CLO2 Chlorine Dioxide Sensor Assembly (0-50ppm)
DM-700-B2H6 Diborane Sensor Assembly
DM-700-C2H5OH Ethanol Sensor Assembly
DM-700-C2H5SH Ethyl Mercaptans Sensor Assembly
DM-700-C2H4 Ethylene Sensor Assembly
DM-700-C2H4O Ethylene Oxide Sensor Assembly
DM-700-F2 Fluorine Sensor Assembly
DM-700-CH2O Formaldehyde Sensor Assembly
DM-700-GeH4 Germane Sensor Assembly
DM-700-N2H4 Hydrazine Sensor Assembly
DM-700-H2 Hydrogen Sensor Assembly (ppm Range)
DM-701-H2 Hydrogen Sensor Assembly (4% Range)
DM-702-H2 Hydrogen Sensor Assembly (1% Range)
DM-700-HBr Hydrogen Bromide Sensor Assembly
DM-700-HCL Hydrogen Chloride Sensor Assembly
DM-700-HCN Hydrogen Cyanide Sensor Assembly
DM-700-HF Hydrogen Fluoride Sensor Assembly
DM-700-H2S Hydrogen Sulfide Sensor Assembly
DM-700-CH3OH Methanol Sensor Assembly
DM-700-CH3SH Methyl Mercaptans Sensor Assembly
DM-700-NO Nitric Oxide Sensor Assembly
DM-700-NO2 Nitrogen Dioxide Sensor Assembly
DM-700-O3 Ozone Sensor Assembly
DM-700-PH3 Phosphine Sensor Assembly
DM-700-SiH4 Silane Sensor Assembly
DM-700-SO2 Sulfur Dioxide Sensor Assembly
Specifications
Sensor Type : Continuous diffusion/adsorption , 3-electrode electrochemical cell , Plug-in field replaceable Intelligent Type
Sensor Life : 3 to 5 years typical
Measurement Range : Various
Accuracy/Repeatability : ±2% FS
Response/Clearing Time : Various
Span Drift : <2% signal loss per month
Outputs : Linear 4-20 mA DC , RS-485 MODBUS-RTU
Electrical Classification
Explosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -40°C to +50°C)
Class I, Zone 1, Group IIC
ATEX
II 2 G Ex d ib IIC T4 Gb (Tamb = -40°C to +50°C)
Ingress Protection : NEMA 4X, IP66
Safety Approvals
CCSAUS Complies with ISA 92.0.01 Part 1-1998; Performance Requirements for H2S
ATEX
CE Marking
SIL2 Certified to IEC 61508
Operating Temperature Range : Various
Storage Temperature Range : Various
Operating Humidity Range : Various
Operating Pressure Range : Various
PI-700-VOC
Introduction
Detcon Model Series 700 industrial gas detectors are a new generation of intelligent sensor modules that incorporate and integrate several leading edge improvements. The sensors are specifically designed for harsh and extreme locations. This new and superior level of environmental durability in sensor design includes an electropolished 316 stainless steel housing, multi-layered transient spike protection circuitry and 100% encapsulated electronics. The sensor electronics are completely protected and immune to water ingress and corrosion. The sensor elements are all plug-in components and can easily be replaced in the field. Operator interface is non-intrusive via a small handheld magnet. Configuration and routine calibration is intuitive and menu driven with fully scripted instructions. Sensor status is displayed on a built-in alphanumeric LED display. Model Series 700 intelligent sensor modules feature dual redundant outputs, a linear 4-20 milliamp analog signal and a Modbus RS-485 serial output.
Specifications
Sensor Type : Continuous diffusion/adsorption , Photo Ionization Detector (PID) , Plug-in replaceable intelligent type (with replacement lamp)
Sensor Life : 2 years typical
Measurement Range : Gas Dependent, ranges as low as 0-10 ppm or as high as 0-5,000ppm (consult Detcon) , Special Low Range 0-500 ppb
Accuracy/Repeatability : ±10% of reading or ±2% of range (greater of )
Response Time T50 <30 seconds; T90 <60 seconds
Outputs : Linear 4-20 mA DC , RS-485 MODBUS-RTU
Electrical Classification
Explosion proof
CSA and US (NRTL)
Class I, Division 1, Groups B, C, D (Tamb = -20°C to +50°C)
Class I, Zone 1, Group IIB+H2
ATEX
II 2 G Ex d ib IIC T4 Gb (Tamb = -20°C to +50°C)
Ingress Protection : NEMA 4X, IP66
Safety Approvals
CCSAUS Performance to ISA 12.13.01-2000 and CSA 22.2 #152
ATEX
CE Marking
Warranty
Plug-in detector - 1 year
Transmitter - 2 Years
Operating Temperature Range : -4°F to +122°F; -20°C to +50°C
Storage Temperature Range : -4°F to +122°F; -20°C to +50°C
Operating Humidity Range : 0-100% RH non-condensing